Facade engineering is the design of a building's outer skin so it carries wind and its own weight back to the structure, keeps water out, and moves with the frame without cracking glass or popping panels. On a commercial project that means curtain walls, storefronts, glazing, metal and composite panels, stone and precast cladding, and the anchors that tie them to the slab edges and columns. Wikipedia's entry on the subject notes that facades are among the most expensive and highest-risk elements of a major project, and historically the part of the building fabric with the most failures.
Owners and architects mostly need to know what the code requires the facade to resist, how stiff its framing must be, and which engineer signs for which part.
On a typical commercial building, the work splits into a few tasks:
Large firms run dedicated facade groups for towers and complex custom systems. On most low- and mid-rise commercial, school and municipal buildings, the work is shared between the structural engineer of record and the specialty engineer who works for the curtain wall or panel contractor.
The 2021 IBC (§1609.1.1) requires wind loads on every building to be determined under Chapters 26 to 30 of ASCE 7, with wind assumed to come from any horizontal direction and pressures acting normal to the surface. Facade elements are designed for the components and cladding pressures, which are higher near corners and roof edges than the pressures used for the main frame.
For glass, IBC §2404.1 applies:, vertical glass (sloped 15 degrees or less from vertical) in windows, curtain walls, storefronts and doors must be designed for the components and cladding wind loads from §1609. The load resistance of the glass is determined under ASTM E1300. Glass in glazed curtain walls and storefronts also has to meet the seismic requirements of ASCE 7 §13.5.9.
Where one or more sides of a pane aren't firmly supported, as in structural glass fins, point-supported glass or butt-glazed corners, §2403.2 requires detailed construction documents, shop drawings, and analysis or test data from a registered design professional.
ASCE 7-22 adds a tornado chapter. ASCE describes the criteria as defending against tornadic winds of up to about 135 mph. Whether it applies to your project depends on the code edition and amendments your city has adopted, so ask the building department early on a school, hospital or emergency facility in North Texas.
Facade framing is often governed by stiffness, not strength. The IBC sets these limits:
| Element | Limit | Code |
|---|---|---|
| Framing supporting glass, span up to 13 ft 6 in | L/175 under 0.6 x components and cladding wind load | IBC §1604.3.7 |
| Framing supporting glass, span over 13 ft 6 in | L/240 + 1/4 in under 0.6 x components and cladding wind load | IBC §1604.3.7 |
| Glass edge support ("firmly supported") | Same L/175 or L/240 + 1/4 in limits on edge deflection | IBC §2403.3 |
| Exterior walls with plaster or stucco | L/360 under wind | IBC Table 1604.3 |
| Exterior walls with other brittle finishes | L/240 under wind | IBC Table 1604.3 |
| Exterior walls with flexible finishes | L/120 under wind | IBC Table 1604.3 |
| Secondary wall members supporting formed metal siding | L/90 under design wind | IBC Table 1604.3, note |
A footnote to Table 1604.3 lets the designer take the wind load for these deflection checks as 0.42 times the components and cladding load, or calculate it directly from the 10-year wind speed. The glass-framing limits in §1604.3.7 still govern where framing supports glass.
The building's own movement matters too. Slab edges deflect under floor load, and floors drift sideways under wind. The facade joints and anchors have to take that movement, which is why the structural engineer of record should give the facade designer the expected slab-edge deflection and story drift in the contract documents.
The IBC's weather protection section (§1402.2) requires a weather-resistant exterior wall envelope with flashing, a water-resistive barrier behind veneers, and a way to drain water that gets into the wall back to the outside. Concrete and masonry walls designed under Chapters 19 and 21 are exempt from the separate envelope requirement. Strength checks won't catch a missing end dam at a sill or a sealant joint too narrow for the movement it has to take, so the shop drawing review should cover drainage and joint sizing as well as the calculations.
Curtain walls and storefronts are usually delegated design: the architect and structural engineer of record set the performance requirements, and the facade contractor's engineer designs the system. Texas law makes the sealing rules clear.
In practice, that produces a split like this:
| Task | Usually done by |
|---|---|
| Performance criteria: loads, drift, deflection limits, slab-edge movement | Structural engineer of record, with the architect |
| Building structure and slab edges that receive anchors | Structural engineer of record |
| Curtain wall or panel system: mullions, glass, anchors, connections | Specialty engineer licensed in Texas, working for the facade contractor |
| Shop drawing and calculation review for conformance with the design intent | Architect and structural engineer of record |
| Field observation of anchors and installation | Engineer of record and specialty engineer, as the contract assigns |
Write the split into the specifications. Gaps show up when nobody is named for the anchor embeds or the steel that supports the facade at an opening.
Isbell Engineering Consultants lists facade engineering, including the design and analysis of curtain walls, glazing systems and cladding, among its structural engineering services, alongside structural design and construction phase services such as shop drawing review. For more on how the structural engineer fits into a commercial project, see what a structural engineer does. If you have a curtain wall, storefront or cladding package to design or review, send the project details through our contact page.
It's the engineering of a building's exterior envelope (curtain walls, glazing, cladding and their anchors) so it resists wind and other loads, stays within deflection limits, keeps water out and accommodates the building's movement.
They set or apply the facade design loads, check glass, framing, panels and connections, design or review anchors, review shop drawings and calculations, and help observe installation. On delegated-design projects, a specialty engineer working for the facade contractor often designs the system itself.
Components and cladding wind pressures under ASCE 7 Chapters 26 to 30, as the IBC (§1609.1.1) requires. Glass resistance is checked under ASTM E1300 (§2404.1).
Under IBC §1604.3.7, framing that supports glass may deflect no more than L/175 for spans up to 13 feet 6 inches, or L/240 plus 1/4 inch for longer spans, under 0.6 times the components and cladding wind load.
Each engineer seals the work they're responsible for. Texas Occupations Code §1001.401 requires the seal on engineering documents for Texas projects, and TBPELS rule 137.33(g) requires each license holder on a shared document to seal it with a note of their work.